8 DXi2500-D Specifications
DXi2500-D Site Planning Guide
Environmental
Specifications 0
Table 9 provides various DXi2500-D environmental specifications.
Table 9 Environmental
Specifications
Climatic Environment
Temperature Operating 10° to 35°C (50° to 95°F) with a maxi-
mum temperature gradation of 10°C per
hour*
Shipping and storage –40° to 65°C (–40° to 149°F) with a
maximum temperature gradation of
20°C per hour
Relative humidity Operating 20% to 80% (noncondensing) with a
maximum humidity gradation of 10% per
hour
Shipping and storage 5% to 95% (noncondensing) with a max-
imum humidity gradation of 10% per
hour
Altitude Operating –16 to 3048 m (–50 to 10,000 ft)
Shipping and storage –16 to 10,600 m (–50 to 35,000 ft)
Heat Operating 2697 BTU/hr maximum
* 35°C (95°F) is the maximum temperature for the DXi2500-D at sea level. For every
1000 feet (305 meters) of altitude, the maximum temperature is reduced by 1° (exam
-
ple: the maximum temperature for a DXi2500-D at 1000 feet (305 meters) is 34°C
(93°F).
Maximum Vibration
Operating 0.26 G at 5–350 Hz for 2 min
Shipping and storage 1.54 G at 10–250 Hz for 15 min
Maximum Shock
Operating One shock pulse in the positive z axis
(one pulse on each side of the system)
of 41 G for up to 2 ms
Shipping and storage Six consecutively executed shock
pulses in the positive and negative x, y,
and z axes (one pulse on each side of
the system) of 71 G for up to 2 ms